> Working pressure: 1 to 5 bar
> Flow: 3 l/min at 3 bars - 4-position setting Anti water-hammer system
> Flow time: 15 seconds - lever upwards or downwards
> Hydraulic supply: 2 PEX hoses DN8 G3/8'' - 350mm
> Thermal resistance: This tap can withstand a thermal shock of 75°C for 30 minutes as part of a thermal shock programme
> Safety: With temperature limiter (at 38°C for cold water at 15°C/3 bar and hot water at 60°C/3 bar)
> Convenience: Soft-touch Two-coloured ergonomic lever, in glass fiber reinforced polymer
> Delivered with: 2 PEX hoses with swivel nut and NF check valves 1 base gasket 2 MM 3/8'' (12x17) stop valves 2 Filter gaskets 1 Fixing bracket > Standards / Approvals: Chrome-plated brass body compliant with standards NF EN1982 / NF EN12164 / NF EN12165 Nickel-Chrome surface treatment compliant with NF EN12540 Neutral Salt Spray (NSS) resistant: 200 h according to NF ISO 9227
Failid
Vajutava nupuga segisti
Presto
Antiblokeerimise süsteemiga
kroom
15 sek. töötsükkel 3 bar
3-6 l/min
Sisu
ALPA
Presto
kroom
30 sek. töötsükkel 3 bar
DESCRIPTION TEMPOFLUX 1 direct flush valve - Ref. 761200
Cross wall time kit for direct flush: Cross wall control, can be cut-to-size.
Soft-touch operation. Time flow ~7 sec.
Vacuum breaker.
Integrated stopcock and flow/volume rate adjuster.
Solid brass body and chrome-plated push-button.
In-line inlet M3/4".
Connection washer Ø 32/55mm.
For walls ≤ 200mm, without tube.
Connector | 3/4" |
---|---|
Length | 200mm |
> Working pressure : 1 to 5 bar
> Flow : 6 l/min at 3 bar - 4-position flow adjustment device Anti-water-hammering design
> Flow time : 15 seconds (± 5 sec.)
> Hydraulic supply : In-line water inlet M G 1/2" Inlet and outlet Cold water
> Thermal resistance : Resistant to a temperature of 75°C for 30 minute thermal shock
> Security : Patented anti-blocking "S" system to avoid the water to flow continuously
> Delivered with : 1 Cross-partition control (1 to 200 mm thick) 1 Short wall spout (Non-rotating fixing) 87 mm 1 Closing tap with S anti-blocking system 1 stop valve M 1/2" (15x21) / M 1/2" (15x21) with quick couplings (12x14 mm) Instruction manual
> Standards & approvals : Brass body in accordance with EN 1982, EN 12164, EN 12156 Molded chrome-plated body in accordance with EN 12540 200-hour neutral salt spray resistant (NSS) in accordance with ISO 922
PREMIX SECURITY
Ref. 731052
Group thermostatic mixing valve for hot water circulating loops adjustable from 44°C to 58°C:
Anti-scalding safety.
Regulates temperature variations.
Non-return valves and filters accessible from the exterior without having to remove the mechanism.
Thermal cartridge with no specific lever needed (push-button on the control knob).
Interchangeable cartridge with thermostatic cell.
High-resistance chrome-plated brass body.
Maximum hot water temperature: 85°C.
Differential hot water / mixed water: 15°C mini.
Pressure differences at the entrance: 1 bar maximum (0.5 bar recommended).
Minimum pressure / maximum: 1 to 10 bar (1 to 5 bar recommended).
Left hand side hot water inlet (red ring) and right hand side cold water inlet (blue ring).
Mixed water outlet at the top (purple ring) for bottom outlet: unscrew / place lid at the top and outlet connector at the bottom.
15% energy savings: optimised heat loss (comparison between a circulating loop at 55°C and a non-circulating system at 70°C).
Safety and prolongation of system life span (Hot water at > 65°C leads to premature aging within the system).
Maximum temperature limiter, can be adjusted by the installer.
Reduced risk of scalding by limiting temperature at the point-of-use.
55 lpm - M3/4".